Q.I would like to connect three drivers to NETC02-CC. Can the driver be set to address number 0, 1, and 3, leaving address number 2 empty?

A.

This is possible. The setting method in the support software MEXE02 is as follows.

Select the RS-485 communication compatible product connection for the parameter.
Number of connected units Selection: Prioritize "Connection (address number)" parameter

Connection (axis #0~3)

  • Connection (axis #0): Effective
  • Connection (axis #1): Effective
  • Connection (axis #2): Disable
  • Connection (axis #3): Effective
MEXE02 setting screen

Product Category: Network compatible products and controllers
Model and Series: NETC02-CC
Description: How to Use/Setting Method
FAQ No.: 540